Time functions | Special functions Y, S, LS
Y - Star–delta timer
The function provides automatic switching from star operation to delta operation.
When S switches ON, the time t starts, and the star output R switches ON.
After t expires, the star output switches OFF and the delta output switches ON.
When S switches OFF, both outputs switch OFF.
S - Step-on / Step-off switch
The function provides stepwise switching with each activation of the trigger.
Each time S switches, the output R changes state for time t.
The trigger has no time-dependent influence.
LS - Step-switching (staircase lighting timer)
The function provides timed activation with optional stop and reset control.
When S is triggered, the time t starts, and the output R switches ON.
When S is triggered again, the time t stops and R switches OFF.
WhenS is triggered again, the time t resets and starts again immediately.
When t expires, the output R switches OFF.