CIM2R/UC24-240V

Current type AC / DC (50 Hz)
Nominal voltage 24 V-240 V

Current consumption on input control B1 AC / DC < 22 mA / < 22 mA
Current consumption on supply A1-A2 AC / DC < 23 mA / < 23 mA
Frequency range 0; 16 ... 63 Hz
Nominal voltage 24 … 240 V AC / DC
Operating voltage range 16.8 … 250 V AC / DC
Power consumption AC / DC 1.2 VA / 430 mW
Threshold voltage on input control B1 AC / DC 13 V / 15 V

Conductor cross section control / main circuit 2.5 mm2, 2 x 1.5 mm2
Housing material PA
Ingress Protection IP 20
Nominal screw torque control / main circuit 0.5 Nm
Operation temperature -40 ... 70 °C
Storage temperature (no ice) -40 ... 85 °C
Weight 70 g

Overvoltage category III
Pollution degree 2
Rated test voltage control / main circuit 2.5 kV rms / 1 min
Rated test voltage open contact 1 kV rms / 1 min

Contact materials AgNi
Inrush current 30 A, 10 ms
Mechanical endurance (cycles) ≥ 30 000 000
Minimum load 10 mA, 10 V
Number of contacts 1 CO
Rated current 16 A
Rated load AC-1 4000 VA
Rated voltage 250 V AC
Switching at zero crossing yes (td > 0.6 s)

Approvals UKCA,CE,cURus,EAC,Railway
Railway EN 50155,EN 45545-2
Standards IEC/EN 61812-1

Timing range 50 ms … 60 h
Timing scale 0.6 s / 6 s / 60 s / 6 min / 60 min / 6 h / 60 h
Approvals
3D-models "CIM2R/UC24-240V"
Documents "CIM2R/UC24-240V"
Time Relay

There are two ways to retrofit an existing industrial relay with timing functions.
Time cubes are ideal when a socket and relay are already installed and only a single timing function needs to be added. The time cube is simply plugged between the socket and the relay and adjusted via DIP switch or potentiometer. It is available for industrial relay series C2 and C3, as well as for the Long Life series C2x and C3x.

Alternatively, time modules can be used. These modules are inserted into the socket’s module compartment and, compared to time cubes, offer more timing functions and longer setting ranges. They are available for sockets S3-M0, S3-M0R, S3-M1, S3-M1R, S5-M, and S5-MR and are compatible with industrial relays C3 and C5, as well as Long Life relays C3x.

Both solutions allow time relays to be configured with up to three changeover contacts – more than is usually possible with standard time relays.

The process is the same for almost all time relays. First, select a function using the potentiometer. Each letter (A, E, W, K, etc.) stands for a specific function, which is described on the side of the relay or on the package insert.

Next, select the time range, whereby the selected range always corresponds to the maximum value. The last potentiometer is then used to fine-tune the time setting. For example, if you want to set a 30-second switch-off delay, it would look like this:

Function: A

Time range: 60 seconds

Fine adjustment: On a scale of 0-6, the potentiometer is then set to 3 (6 = 60 seconds, 3 = 30 seconds, 1 = 10 seconds).

E – On delay 

The function provides a delayed switching ON of the output. 
When switches ONthe time t starts. 
After expiresthe output R switches ON. 
If switches OFF before t endsstays OFF. 


A – Off delay 

The function provides a delayed switching OFF of the output. 
When switches ONthe output R switches ON immediately. 
When switches OFFthe time t starts. 
After expiresthe output R switches OFF.

 

F – On and off delay 

The function provides a delayed switching ON and a delayed switching OFF of the output. 
When switches ONthe on delay t₁ starts. 
After t₁ expiresthe output R switches ON. 
When switches OFFthe off delay t₂ starts. 
After t₂ expiresthe output R switches OFF.
 

W – One shot leading edge 

The function provides a fixed output pulse on the leading edge of the trigger. 
When switches ONthe output R switches ON for time t. 
After expiresswitches OFFindependent of S. 
When switches OFFswitches OFF. 


N – One shot trailing edge 

The function provides a fixed output pulse on the trailing edge of the trigger. 
When switches ONdoes not change. 
When switches OFFthe output R switches ON for t. 
After expiresswitches OFF. 


Q – One shot leading and trailing edge 

The function provides fixed output pulses on both the leading and trailing edges of the trigger. 
When switches ONthe output R switches ON for t1. 
After t1 expiresswitches OFF. 
When switches OFFthe output R switches ON again for t2. 
After t2 expiresswitches OFF.
 

K – Pulse shaping 

The function provides a fixed output pulse independent of the input duration. 
When switches ON (pulse or continuous), the output R switches ON for t. 
During t, has no influence on R. 
After expiresswitches OFF. 


L – Pulse shapingretrigger 

The function provides a fixed output pulse that restarts when retriggered. 
When switches ONthe output R switches ON for t. 
If triggers again during tthe time t restarts from zero. 
After the final expiresswitches OFF. 


M – Puls shaping 

The function provides a fixed output pulse after S switches OFF. 
When switches ONremains OFF. 
When switches OFFthe output R switches ON for t. 
After expiresswitches OFF.
 

B – Indicator, pulse start 

The function provides periodic ON and OFF switching starting with an ON pulse. 
When switches ONthe output R switches ON for time t, then switches OFF for time t. 
switches ON and OFF periodically until switches OFF. switches OFF with S. 


B1 – Indicator, pulse starttrailing pulse 

The function provides periodic ON and OFF switching starting with an ON pulse and ending with a trailing pulse. 
the output R switches ON for time t, then switches OFF for time t. 
switches ON and OFF periodically until switches OFF. 
When switches OFFthe output R switches ON once more for tthen switches OFF. 


B2 – Indicator, interval start 

The function provides periodic ON and OFF switching starting with an OFF interval. 
When switches ONthe output remains OFF for t, then R switches ON for time t. 
switches ON and OFF periodically until switches OFF. switches OFF with S. 

G – On delay single shot 

The function provides an output pulse after a delay. 
When switches ONthe delay t₁ starts. 
After t₁ expiresthe output R switches ON for t₂. 
After t₂ expiresswitches OFF. 

During t₂has no influence on R. 


H – On delay single shot 

When switches ONthe delay t₁ starts. 
After t₁ expiresthe output R switches ON for t₂. 
After t₂ expiresswitches OFF. 
When switches OFFswitches OFF
 

I – Repeat cycle timer, pulse start 

The function provides periodic ON and OFF switching starting with an ON pulse. 
When switches ONthe output R switches ON for t₁. 
After t₁ expiresswitches OFF for t₂. 
Afterwards switches ON and OFF periodically according to t₁ and t₂. 
When switches OFFswitches OFF. 


P – Repeat cycle timerinterval start 

The function provides periodic ON and OFF switching starting with an OFF interval. 
When switches ONthe delay t₁ starts, and remains OFF for t₁. 
After t₁ expiresthe output R switches ON for t₂. 
Afterwards switches ON and OFF periodically according to t₁ and t₂. 
When switches OFFswitches OFF. 

Y - Star–delta timer 

The function provides automatic switching from star operation to delta operation. 
When switches ONthe time t starts, and the star output R switches ON. 
After expiresthe star output switches OFF and the delta output switches ON. 
When switches OFFboth outputs switch OFF. 


S - Step-on / Step-off switch 

The function provides stepwise switching with each activation of the trigger. 
Each time switchesthe output R changes state for time t. 
The trigger has no time-dependent influence. 


LS - Step-switching (staircase lighting timer) 

The function provides timed activation with optional stop and reset control. 
When is triggeredthe time t starts, and the output R switches ON. 
When is triggered againthe time t stops and R switches OFF. 
WhenS is triggered againthe time t resets and starts again immediately. 
When expiresthe output R switches OFF. 

U – Pulse sequence monitoring 

The function provides monitoring of pulse separation and triggers an alarm if pulses are too close togetherIf the separation becomes smaller than the set time tP, an alarm output is activated after an additional delay tV. 
The monitoring starts with S1 or S2. 
If the pulse separation of P is smaller than tP, an alarm output is activated after the alarm delay tV. 
If the pulse separation is larger than tPno alarm is triggered. 
The start‑up behaviour depends on the selected input S1 (Monitoring begins immediately with the first pulse. There is no suppression of alarm monitoring during start‑up.) or S2 (Monitoring begins after the short‑out time tA to prevent false alarms during system start-up) 

 

V – Pulse sequence monitoring 

The function provides monitoring of pulse separation and triggers an alarm if pulses are too far apart. 
The monitoring starts with S1 or S2. 
If the pulse separation of P is larger than tP, an alarm output is activated after the alarm delay tV. 
If the pulse separation is smaller than tPno alarm is triggered. 
The start‑up behaviour depends on the selected input S1 (without start‑up short‑out tA) or S2 (with start‑up short‑out tA).