Skip to main content Skip to search Skip to main navigation

CRINT-C132R/UC110-125V

Current type AC / DC (50 Hz)
Nominal voltage 110 V-125 V

Operating voltage range 0.8 UN … 1.25 UN
Pick-up voltage ≤ 0.8 UN
Power consumption AC / DC 0.9 VA / 0.4 W
Release voltage ≥ 0.1 UN

Variant Push-in

- Multi wire (crimped) 0.34 mm2 / AWG 22 … 1.5 mm2 / AWG 16
- Multi wire (un-crimped) 0.34 mm2 / AWG 22 … 2.5 mm2 / AWG 14
- Single wire 0.34 mm2 / AWG 22 … 2.5 mm2 / AWG 14
Conductor cross section cage clamp 0.75 … 2.5 mm2
Conductor cross section control / main circuit Push-in terminal
Housing material PA
Ingress Protection IP 20
Mounting TH35 (EN 60715)
Operation temperature -40 … 70 °C (-40 ... 55 °C for control voltage > 60 V)
Pick-up time / bounce time 7 ms / ≤ 8 ms
Release time / bounce time 15 ms / ≤ 4 ms
Storage temperature (no ice) -40 … 85 °C
Weight 30 g

Overvoltage category III
Pollution degree 3
Test voltage contact / coil 4 kV / 1 min
Test voltage open contact 1 kV / 1 min

Electrical endurance at rated load AC-1 (cycles) ≥ 10 000
Inrush current 15 A, 2.5 ms
Maximum contact load AC 6A / 250 V AC-1
Maximum contact load DC 6A / 30 V DC-1
Mechanical endurance (cycles) ≥ 1 000 000
Rated current 6 A
Rated load AC 1 500 VA
Recommended minimum contact load 10 mA / 5 V

Approvals UKCA,CE,EAC,Railway,cURus
Railway EN 50155,EN 45545-2
Standards IEC/EN 61810-1,EN 60664-1
Approvals
Documents "CRINT-C132R/UC110-125V"
Skip product gallery

Accessories

CRINT-BR20-BU (BAG 5 PCS)
CRINT-BR20-BU (BAG 5 PCS)
Connecting comb 20-fold (5 pcs.)

CRINT-BR20-RD (BAG 5 PCS)
CRINT-BR20-RD (BAG 5 PCS)
Connecting comb 20-fold (5 pcs.)

CRINT-BR20-BK (BAG 5 PCS)
CRINT-BR20-BK (BAG 5 PCS)
Connecting comb 20-fold (5 pcs.)

CRINT-LAB (BAG 4X16 PCS)
CRINT-LAB (BAG 4X16 PCS)
Labelling plate (4x16 pcs.)

BS11-PI (50m tape)
BS11-PI (50m tape)
Labelling strip (50m)