CRINT-C131/UC12V
| Current type | AC / DC (50 Hz) |
|---|---|
| Nominal voltage | 12 V |
| Operating voltage range | 0.8 UN … 1.25 UN |
|---|---|
| Pick-up voltage | ≤ 0.8 UN |
| Power consumption AC / DC | 0.9 VA / 0.4 W |
| Release voltage | ≥ 0.1 UN |
| Variant | Push-in |
|---|
| - Multi wire (crimped) | Backup information: 2 x 0.34 mm2 / AWG 22 … 2 x 1.5 mm2 / AWG 16 Use copper conductors only Max. jacket diameter 4.0 mm Stripping length 8 mm |
|---|---|
| - Multi wire (un-crimped) | Backup information: 2 x 0.34 mm2 / AWG 22 … 2 x 2.5 mm2 / AWG 14 Use copper conductors only Max. jacket diameter 4.0 mm Stripping length 8 mm |
| - Single wire | Backup information: 2 x 0.34 mm2 / AWG 22 … 2 x 2.5 mm2 / AWG 14 Use copper conductors only Max. jacket diameter 4.0 mm Stripping length 8 mm |
| Conductor cross section cage clamp | 0.75 … 2.5 mm2 |
| Conductor cross section control / main circuit | Push-in terminal |
| Conductor cross section screw terminal | 0.34 ... 2.5 mm2 |
| Housing material | PA |
| Ingress Protection | IP 20 |
| Mounting | TH35 (EN 60715) |
| Operation temperature | -40 … 70 °C (-40 ... 55 °C for control voltage > 60 V) |
| Pick-up time / bounce time | 7 ms / ≤ 8 ms |
| Release time / bounce time | 15 ms / ≤ 4 ms |
| Storage temperature (no ice) | -40 … 85 °C |
| Weight | 30 g |
| Overvoltage category | III |
|---|---|
| Pollution degree | 3 |
| Test voltage contact / coil | 4 kV / 1 min |
| Test voltage open contact | 1 kV / 1 min |
| Electrical endurance at rated load AC-1 (cycles) | ≥ 10 000 |
|---|---|
| Inrush current | 15 A, 2.5 ms |
| Maximum contact load AC | 6 A / 250 V AC-1 |
| Maximum contact load DC | 6 A / 30 V DC-1 |
| Mechanical endurance (cycles) | ≥ 1 000 000 |
| Rated current | 6 A |
| Rated load AC | 1 500 VA |
| Recommended minimum contact load | 100 mA / 12 V |
| Approvals | UKCA,CE,EAC,cULus,cURus |
|---|---|
| Standards | IEC/EN 61810-1,EN 60664-1 |
Approvals
Documents "CRINT-C131/UC12V"