CRINT-C125R/DC24V

Current type DC
Nominal voltage 24 V

Operating voltage range 0.8 … 1.2 UN
Pick-up voltage ≤ 0.8 UN
Power consumption AC / DC 160 mW
Release voltage ≤ 0.25 UN

Variant Cage clamp terminal

Conductor cross section cage clamp 0.75 … 2.5 mm2
Housing material PA
Ingress Protection IP 20
Mounting TH35 (EN 60715)
Operation temperature -30 … 70 °C
Pick-up time ≤ 50 μs
Release time ≤ 300 μs
Weight 30 g

Overvoltage category III
Pollution degree 3
Test voltage contact / coil 2.5 kV / 1 min
Test voltage open contact 1 kV / 1 min

SSR-Typ MOSFET
Inrush current 48 A, 10 ms
Maximum voltage drop 0.35 V DC
Output type MOSFET
Output voltage range 3 ... 28.8 V DC
Rated current 4 A
Rated load DC 115 W
Recommended minimum contact load 20 mA / 5 V
Residual current 0.1 mA
Type Instantaneous

Approvals UKCA,CE,EAC,Railway
Railway EN 50155,EN 45545-2
Standards EN 62314
Approvals
Documents "CRINT-C125R/DC24V"
Skip product gallery

Accessories

CRINT-BR20-BU (BAG 5 PCS)
CRINT-BR20-BU (BAG 5 PCS)
Connecting comb 20-fold (5 pcs.)

CRINT-BR20-RD (BAG 5 PCS)
CRINT-BR20-RD (BAG 5 PCS)
Connecting comb 20-fold (5 pcs.)

CRINT-BR20-BK (BAG 5 PCS)
CRINT-BR20-BK (BAG 5 PCS)
Connecting comb 20-fold (5 pcs.)

CRINT-LAB (BAG 4X16 PCS)
CRINT-LAB (BAG 4X16 PCS)
Labelling plate (4x16 pcs.)